CRIR E1(C06-0800-000) Honeywell CO2 Sensor

Available on order
For Bulk requirement, Kindly click on enquiry now button

 

Product Details:

Product Description
Brand Honeywell
Model no. CRIR E1(C06-0800-000)
Target gas carbon dioxide (CO2)
Operating principle non-dispersive infrared (NDIR)
Standard range1, 2 400 ppm to 2000 ppm, up to 10000 ppm extended range
Measurement interval 4 s
Accuracy 3 ±50 ppm ±5% of reading
Typical response time (T90) <120 s
Sensor warm-up time 3 min typical
Repeatability >97%
Operating voltage 4.5 V to 5.5 V unprotected against surges and reverse connection
Power consumption 300 mA peak, 30 mA average
Alarm output, open collector 1000 ppm/800 ppm normal state is conducting max 100 mA.
Transistor open at CO2 high or at sensor failure (see Figure 1).
Serial communication5 UART, Modbus protocol
Operating temperature range 0°C to 50°C
Storage temperature range -40°C to 70°C
Operating humidity 0 %RH to 90 %RH non-condensed
Expected operating life 10 years
Maintenance6 maintenance-free for normal indoor applications
Weight <8 g
Dimensions 33 mm x 22 mm X 11,2 mm (tolerance ±0,5 mm)

Above specifications mentioned are for quick reference only. Actual technical details has to be obtained from below catalog.

brochure

Description

CRIR E1(C06-0800-000) Honeywell CO2 Sensor

The CRIR E1 Commercial Carbon Dioxide (CO2) sensor is a single channel, non-dispersive infrared (NDIR) sensor. Within the CRIR E1 is a sensing chamber with an infrared source at one end and a detector fitted with an optical filter at the other end. The source emits radiation at wavelengths which include the absorption band of CO2. The filter blocks wavelengths which are not sensitive to the presence of CO2, thereby increasing selectivity and sensitivity. As the light passes through the sensing chamber, a fraction is absorbed if CO2 is present. The difference between the light emitted by the source and received by the detector can then be converted to a CO2 concentration reading.

Reviews

There are no reviews yet.

Be the first to review “CRIR E1(C06-0800-000) Honeywell CO2 Sensor”

Your email address will not be published. Required fields are marked *

Post comment